  FEATURES
● Microprocessor-controlled.
● Measures the voltage drop as if 16A was flowing between Line and
   Neutral.
● Displays voltage without current (V at 0A).
● Display voltage as if 16A flowing between Line and Neutral (V at
   16A).
● Loop test for L-E
● PSC between L-N.
● Single one smart push button operation; ON, Scroll through results
   and menus.
● Checks wiring integrity (LEDs).
● Auto off/auto ranging (software range).
● Combined prospective short circuit current, loop and load tester.
● Display can be customized for large orders.
  SPECIFICATIONS
Loop impedance range L-E : 0.03-2000Ω(Software Ctrl)
Test currents in each loop : 11.76A at 230V / 50Hz
Voltage measurement L-N : 50 to 280V AC (Sine)
Load current for volt drop    
(L-N) : 16A (Calculation)
Neutral wire resistance : (Not available, see 1826 NA)
Line wire resistance &    
transformer windings : (Not available, see 1826 NA)
PSC current(L-N) max : 6kA at 230Vac supply
PSC current(L-E) max : (Not available, see 1826 NA)  
Operating voltage : 230V±20 at 50Hz Sine
Typical Accuracy    
Loop impedance : 5%rdg ± 2dgt
PSC current : 12%rdg ± 5dgt
Voltage : 3%rdg ±1dgt
Operating-temperature    
-humidity : -10°C to +40°C 80% Max.
    relative humidity 
Dimensions : 170(L) x 165(W) x 92(D) mm
Weight (battery included) : Approx. 970g
Power source : 1.5V (AA) x 8
Safety standard : EN 61010-1 CAT III 300V
    EN 61326-1
     
 